Maximum Number of Conductors in Rigid Metal Conduit
| Type Letters |
THHN, THWN, THWN-2 |
Cond. Size AWG/kcmil |
Trade Sizes in Inches |
|
| 0.50 |
0.75 |
1.00 |
1.25 |
1.50 |
2.00 |
2.50 |
3.00 |
3.50 |
4.00 |
5.00 |
6.00 |
| 14 |
13 |
22 |
36 |
63 |
85 |
140 |
200 |
309 |
412 |
531 |
833 |
1202 |
12 |
9 |
16 |
26 |
46 |
62 |
102 |
146 |
225 |
301 |
387 |
608 |
877 |
10 |
6 |
10 |
17 |
29 |
39 |
64 |
92 |
142 |
189 |
244 |
383 |
552 |
8 |
3 |
6 |
9 |
16 |
22 |
37 |
53 |
82 |
109 |
140 |
221 |
318 |
6 |
2 |
4 |
7 |
12 |
16 |
27 |
38 |
59 |
79 |
101 |
159 |
230 |
4 |
1 |
2 |
4 |
7 |
10 |
16 |
23 |
36 |
48 |
62 |
98 |
141 |
3 |
1 |
1 |
3 |
6 |
8 |
14 |
20 |
31 |
41 |
53 |
83 |
120 |
2 |
1 |
1 |
3 |
5 |
7 |
11 |
17 |
26 |
34 |
44 |
70 |
100 |
1 |
1 |
1 |
1 |
4 |
5 |
8 |
12 |
19 |
25 |
33 |
51 |
74 |
1/0 |
1 |
1 |
1 |
3 |
4 |
7 |
10 |
16 |
21 |
27 |
43 |
63 |
2/0 |
0 |
1 |
1 |
2 |
3 |
6 |
8 |
13 |
18 |
23 |
36 |
52 |
3/0 |
0 |
1 |
1 |
1 |
3 |
5 |
7 |
11 |
15 |
19 |
30 |
43 |
4/0 |
0 |
1 |
1 |
1 |
2 |
4 |
6 |
9 |
12 |
16 |
25 |
36 |
250 |
0 |
0 |
1 |
1 |
1 |
3 |
5 |
7 |
10 |
13 |
20 |
29 |
300 |
0 |
0 |
1 |
1 |
1 |
3 |
4 |
6 |
8 |
11 |
17 |
25 |
350 |
0 |
0 |
1 |
1 |
1 |
2 |
3 |
5 |
7 |
10 |
15 |
22 |
400 |
0 |
0 |
1 |
1 |
1 |
2 |
3 |
5 |
7 |
8 |
13 |
20 |
500 |
0 |
0 |
0 |
1 |
1 |
1 |
2 |
4 |
5 |
7 |
11 |
16 |
600 |
0 |
0 |
0 |
1 |
1 |
1 |
1 |
3 |
4 |
6 |
9 |
13 |
700 |
0 |
0 |
0 |
1 |
1 |
1 |
1 |
3 |
4 |
5 |
8 |
11 |
750 |
0 |
0 |
0 |
0 |
1 |
1 |
1 |
3 |
4 |
5 |
7 |
11 |